PAGE/NUMPAGES变压器容量计算表名称组别额定功率输入容量需要系数功率因数功率因数正切有功功率无功功率视在功率低压额定电流10kV额定电流有功功率同期系数(0.8~0.9)无功功率同期系数(0.93~0.97)无功功率补偿率用电设备Pe(kW)S(kV.A)KxcosφtgφPjs(kW)Qjs(kvar)Sjs(kV.A)Ijs(A)Igs(A)KpKq△qc刮板运输机40T320 0.600.701.02192.00195.88274.29 煤电钻4.8 0.600.701.022.882.944.11 锚杆机具22.5 0.600.701.0213.5013.7719.29 皮带运输机188 0.600.701.02112.80115.08161.14 综掘机190 0.600.701.02114.00116.30162.86 综掘机130 0.600.701.0278.0079.58111.43 工作面溜子220440 0.600.701.02264.00269.33377.14 皮带输送机160 0.600.701.0296.0097.94137.14 乳化液泵150 0.600.701.0290.0091.82128.57 水泵320 0.800.850.62256.00158.65301.18 绞车JD-40160 0.600.701.0296.0097.94137.14 绞车JD-11.468.4 0.600.701.0241.0441.8758.63 皮带125 0.600.701.0275.0076.52107.14 皮带220 0.600.701.02132.00134.67188.57 猴车360 0.600.701.02216.00220.36308.57 耙斗装岩机17 0.600.701.0210.2010.4114.57 无极绳绞车75 0.600.701.0245.0045.9164.29 合计2950.70 1834.421768.972548.40 同时系数 0.701.021650.981680.522355.823579.29 0.900.95 电容补偿 1137.87 0.69电容补偿后 0.950.331650.98542.651737.872640.42 功率损耗 17.3886.89 总计 0.710.94 1668.36629.541783.182709.27 30~16000kV.A容量变压器2500 3608.44144.34 变压器负荷率0.75~0.850.71 变压器应选容量为 2500 kV.A 无功补偿容量为 1138kvar友情提示: