木京水电站UPS蓄电池放电试验
报告
软件系统测试报告下载sgs报告如何下载关于路面塌陷情况报告535n,sgs报告怎么下载竣工报告下载
电池放电记录:放电电流:30A 放电时间:35分钟 试验时间:2015年3月17日电池号数放电前(V)17:3517:4618:0018:10112.812.2712.2612.2511.51212.7812.2912.2812.2711.51312.6611.659.679.668.79412.8112.3012.3012.2911.60512.406.786.806.805.34612.6412.0612.1212.1011.49712.6812.1812.1712.1611.37812.7012.1812.1612.1411.27912.7212.2312.2312.2111.561012.7512.2712.2712.2511.541110.019.459.519.538.551212.6512.1812.1812.1611.611312.7112.2012.2012.1811.501412.7112.2312.2212.2011.451510.066.886.96.915.271612.7012.2412.2312.2111.591712.7512.2912.2812.2711.581812.7212.2412.2312.2211.521912.7012.2512.2512.2311.552012.599.649.689.648.61总电压(V)249.8227.8225.9225.6209.2试验结论:#3、#5、#11、#15、#20蓄电池电压下降较快主检人员: 校核人员: