给水管网课程设计
说明书
房屋状态说明书下载罗氏说明书下载焊机说明书下载罗氏说明书下载GGD说明书下载
姓名:xxx
班级:xxxxxx
学号:xxxxxxxx
专业:给水排水
工程
路基工程安全技术交底工程项目施工成本控制工程量增项单年度零星工程技术标正投影法基本原理
目 录
Ⅰ. 给水管网课程设计任务
书
关于书的成语关于读书的排比句社区图书漂流公约怎么写关于读书的小报汉书pdf
·········································3
1、 设计项目·····················································3
2、 设计资料·····················································3
三、设计任务及成果················································ 3
Ⅱ. 给水管网设计计算说明书·········································4
1、 给水管的定线与布置···········································4
2、 设计用水量的计算 ············································4
2.1基础数据···················································4
2.2 最高日设计用水量的计算····································4
2.3最高日最高时设计用水量的计算·······························5
3、 经济管径的确定···············································5
3.1沿线流量及节点流量的计算···································6
3.2泵站设计供水流量的计算·····································6
3.3水塔设计供水流量的计算·····································7
3.4最高时管段沿线流量分配与节点设计流量计算······················7
3.5初始分配流量及管径的确定·········································8
四、管网水力计算···························································8
4.1摩阻系数的确定·····················································9
4.2管网平差··························································10
Ⅲ参考文献·································································12
Ⅳ附录
附录一、城市最高日用水量变化曲线
附录二、管段平差计算表
附录三、给水管网布置图
附录四、水力计算成果图
Ⅰ. 给水管网课程设计任务书
一、设计项目
某市开发区给水管网初步设计
二、设计资料
1、该小城区道路工程规划图一张
2、该街区居民区最高日综合用水量
标准
excel标准偏差excel标准偏差函数exl标准差函数国标检验抽样标准表免费下载红头文件格式标准下载
3、 居住区人口密度为
4、工厂甲的集中用水设计流量是(每增加一个学号,该集中用水量增加);
工厂乙的集中用水设计流量是(每增加一个学号,该集中用水量增加);
工厂丙的集中用水设计流量是(每增加一个学号,该集中用水量增加);
城市浇洒道路用水定额采用1.5L/(m2.d),市政绿化广场用水定额2.0 L/(m2.d),每天浇洒一次。
5、时变化系数1.42 (每增加一个学号,该值加0.01)
6、最小服务水压为20m
三、设计任务及成果
1、给水管网设计计算
① 设计基本数据的选择;
② 给水管的定线与布置以及
方案
气瓶 现场处置方案 .pdf气瓶 现场处置方案 .doc见习基地管理方案.doc关于群访事件的化解方案建筑工地扬尘治理专项方案下载
的选择;
③ 给水管道设计计算;
2、设计成果
① 设计计算书
计算依据:重要的基础数据、有关规范规定,可列在表格内
计算方法:列出主要的计算公式,说明重要的参数的选取依据
计算过程:列出计算步骤
计算结果:列出重要的计算结果
计算书应计算正确,并附有工艺简图,标注所计算的尺寸
② 绘制给水管道平面布置图和水力计算成果图;
Ⅱ. 给水管网设计计算说明书
一、给水管的定线与布置
根据所给资料,结合城镇规划并考虑经济性和供水可靠性的要求,决定了采用环状给水的布置形式,并在管网中布置水塔,水厂至管网采用双管输水。
其中工厂甲和丙有节点5供水,工厂乙由节点4供水,集水管的具体布置形式见附录一。
二、设计用水量的计算
2.1基础数据
1、开发区浇洒道路实际面积N3a:121482.25m2 (由CAD根据比例尺测得,下同)
2、市政广场实际面积N3b:173792.5 m2
3、居民区实际面积:4277422.44m2=427.7hm2
4、居住区人口N1:200cap/ hm2×427.7 hm2=85540 cap
5、时变化系数Kh:1.45
6、工厂甲的集中用水设计流量是28L/S=2419.2m3/d
工厂乙的集中用水设计流量是26 L/S=2246.4 m3/d
工厂丙的集中用水设计流量是36 L/S=3110.4 m3/d
7、城市浇洒道路用水定额q3a为1.5L/(m2.d),市政绿化广场用水定额q3b为2.0 L/(m2.d),每天浇洒一次。
8、居住区人口密度为200cap/hm2
9、该街区居民区最高日综合用水量标准q1=260L/人·日
10、最小服务水压为20m
2.2最高日设计用水量的计算
1)城市最高日综合生活用水量:
Q1=∑=∑=22240.4(m3/d)
2)工业企业生产用水和职工生活用水量:
将各集中用水户的最高日用水量相加即为工企业和职工生活用水量,取各集中用水户最高日用水量时变化系数为1.45。
Q2=(2419.2+2246.4+3110.4) /1.45= 5362.76m3/d
3)浇洒道路和绿化用水量:
Q3=∑
=∑
=529.8(m3/d)
4)未预见水量和管网漏失水量(取20%):
Q4=0.2×(Q1+ Q2+ Q3)=0.2×(22240.4+5362.76+529.8)=5626.59(m3/d)
5)消防用水量:
查附表3得,消防用水量定额为35L/s,同时火灾次数为2,则消防用水量为:
Q5=q5f5=35×2=70 L/s
最高日设计用水量:
Qd=Q1+Q2+Q3+Q4=22240.4+5362.76+529.8+5626.59=33759.55(m3/d)
取Qd=33760(m3/d)
2.3最高日最高时设计用水量
Qh=Kh ×Qd/86.4(时变化系数由原始资料知Kh=1.45)
=1.45×33760/86.4
=566.57 (L/s)
三、经济管径确定
3.1沿线流量及节点流量的计算
从整个城区管网分布情况来看,干管的分配比较均匀,故按长度流量法计算。
配水干管计算长度:
二级泵站-1为输水管,不参与配水,水塔输水管其配水长度为零。管段3、5、6、12、16、23为单侧配水,其配水长度按实际长度的一半计入。其余均为双侧配水管段,均按实际长度计入。
先计算比流量[L/(s·m)]
最高日最高时用水量为:Qh =566.57 (L/s)
总集中用水流量为:∑qni=28+36 +26=90 (L/s)
配水干管总长度:
∑Lmi=0+949+224+809+506+380+974+420+282+854+832+388
+332+382+845+203+530+447+800+392+636+652+351+306+325+575+836+0
=14230m
比流量ql===0.0335(L/s)
3.2泵站设计供水流量的计算:
最高日设计用水量Qd=33760(m3/d)
泵站设计供水流量为qs1=33760×4.97%×1000÷3600=466 (L/s)
3.3水塔设计供水流量的计算:
Qs21=566.57-466=100.57 (L/s)
3.4最高时管段沿线流量分配与节点设计流量计算
计算结果见下表:
管段沿线流量计算表
管段编号
管段长度/m
管段配水长度/m
比流量/L/(s.m)
管段沿线流量/L/s
[1]
94
0
0.0335
0.00
[2]
949
949
31.79
[3]
448
224
7.50
[4]
809
809
27.10
[5]
1012
506
16.95
[6]
760
380
12.73
[7]
974
974
32.63
[8]
420
420
14.07
[9]
282
282
9.45
[10]
854
854
28.61
[11]
832
832
27.87
[12]
775
388
13.00
[13]
332
332
11.12
[14]
382
382
12.80
[15]
845
845
28.31
[16]
405
203
6.80
[17]
530
530
17.76
[18]
447
447
14.97
[19]
800
800
26.80
[20]
392
392
13.13
[21]
349
0
0.00
[22]
636
636
21.31
[23]
652
652
21.84
[24]
702
351
11.76
[25]
306
306
10.25
[26]
325
325
10.89
[27]
575
575
19.26
[28]
836
836
28.01
合计
16723
14230
476.71
节点设计流量计算表
节点编号
集中流量/(L/s)
沿线流量(L/s)
供水流量(L/s)
节点流量/(L/s)
1
0
466
-466
2
19.65
19.65
3
25.78
25.78
4
26
14.84
40.84
5
64
29.18
93.18
6
50.84
50.84
7
41.96
40.96
8
4.72
4.72
9
5.56
5.56
10
33.75
33.75
11
43.37
47.84
12
24.05
23.05
13
22.68
22.68
14
39.76
39.76
15
24.71
24.71
16
0.00
100.57
-100.57
17
5.13
5.13
18
21.22
20.22
19
40.00
38.39
20
9.63
9.63
21
19.88
19.88
合计
90
476.71
566.57
0
3.5 初始分配流量及管径的确定
根据节点流量连续性方程和供水的经济型与可靠性,
初始分配流量如下表:
初分配流量及管径计算表
管段编号
初分配流量(L/s)
经济流速(m/s)
计算管径(mm)
设计管径D(mm)
[1]
466
1.8
574.3
600×2
[2]
180
1.5
391.0
400
[3]
266.35
1.5
475.6
450
[4]
100.57
1.5
292.2
300
[5]
140
1.5
344.8
350
[6]
99.16
1.0
355.4
350
[7]
24.05
1.0
175.0
200
[8]
54.32
1.4
222.3
200
[9]
4.72
0.6
100.1
100
[10]
80
0.9
336.5
350
[11]
80
1.0
226.4
200
[12]
30.03
0.8
218.7
200
[13]
5.56
0.6
108.6
100
[14]
10
0.8
126.2
125
[15]
6.16
0.8
99.0
100
[16]
13.14
0.8
144.6
150
[17]
36
0.8
239.4
250
[18]
30.69
0.7
236.3
250
[19]
25
0.8
199.5
200
[20]
71.55
1.0
301.9
300
[21]
100.57
1.0
357.9
350
[22]
35
0.8
236.1
250
[23]
42.79
0.8
261.0
250
[24]
15.46
0.8
156.9
150
[25]
5.13
0.6
104.4
100
[26]
9.65
0.6
143.1
150
[27]
9.63
0.6
143.0
150
[28]
4.42
0.6
96.9
100
四、管网水力计算
4.1摩阻系数的确定
在用哈代克罗斯法平差的过程中,算管段压降的时候要先知道管道的摩阻系数,因此先算管到的摩阻系数,这里采用水头公式的指数形式来计算,即hf=s*qn=k*qnL/Dm,所以s= kL/Dm,其中k=10.67/Cw1.852,n=1.852,m=4.87,计算结果见下表:
管段编号
Cw(焊接钢管)
参数k
管长L(m)
管径D(mm)
参数m
摩阻系数s
[1]
120
0.0015
94
600×2
4.87
0.48
[2]
949
400
123.40
[3]
448
450
32.83
[4]
809
300
427.03
[5]
1012
350
252.15
[6]
760
350
189.36
[7]
974
200
3703.69
[8]
420
250
538.73
[9]
282
100
31357.42
[10]
854
300
450.78
[11]
832
200
439.17
[12]
775
200
2946.98
[13]
332
100
36917.25
[14]
382
125
14328.57
[15]
845
100
93961.07
[16]
405
150
6251.47
[17]
530
250
679.83
[18]
447
250
573.36
[19]
800
200
3042.04
[20]
392
300
206.92
[21]
349
350
86.96
[22]
636
250
815.79
[23]
652
250
836.32
[24]
702
150
10835.87
[25]
306
100
34026.14
[26]
325
150
5016.61
[27]
575
150
8875.54
[28]
836
100
92960.30
4.2管网平差
利用excel表格进行平差,具体平差过程及水力计算结果见附录。
得到以下数据:
管段数据:
管段编号
管段长度(m)
管段流量(L/s)
管径(mm)
管内流速(m/s)
管段压降h(m)
[1]
94
466
600×2
0.98
-42.32
[2]
949
207
400
1.65
6.72
[3]
448
238.55
450
1.50
2.31
[4]
809
76.77
300
1.09
3.68
[5]
1012
136
350
1.41
6.27
[6]
760
95.16
350
0.99
2.43
[7]
974
21.99
200
0.70
3.15
[8]
420
20.06
200
0.64
0.14
[9]
282
4.72
100
0.60
1.91
[10]
854
142.07
350
1.48
3.51
[11]
832
24
200
0.76
0.44
[12]
775
23.97
200
0.76
2.94
[13]
332
5.56
100
0.71
2.49
[14]
382
8.48
125
0.69
2.09
[15]
845
7.23
100
0.92
10.18
[16]
405
8.14
150
0.60
1.94
[17]
530
22.60
250
0.63
0.61
[18]
447
94.28
250
1.92
5.12
[19]
800
28.52
200
0.91
4.19
[20]
392
125.95
300
1.78
4.46
[21]
349
100.57
350
1.05
1.84
[22]
636
29.48
250
0.60
1.19
[23]
652
35.07
250
0.71
1.69
[24]
702
13.99
150
0.79
3.99
[25]
306
5.13
100
0.65
5.14
[26]
325
18.85
150
1.07
3.21
[27]
575
9.63
150
0.62
2.43
[28]
836
5.89
100
0.75
6.90
节点数据:
(为了方便计算,取4号节点的地面标高为10米,根据等高线高差得到各节点标高。)
节点编号
节点水头(m)
地面标高(m)
自由水压(m)
节点流量/(L/s)
1
5.77
10.20
-
-466
2
48.09
10.30
37.79
19.65
3
45.78
10.30
35.48
25.78
4
39.51
10.00
29.51
40.84
5
37.08
10.80
26.28
93.18
6
40.23
11.20
29.03
50.84
7
40.37
11.40
28.97
40.96
8
38.46
11.50
26.96
4.72
9
34.37
12.30
22.07
5.56
10
36.86
11.95
24.91
33.75
11
34.77
11.80
22.97
47.84
12
24.59
11.52
13.07
23.05
13
22.65
12.20
10.45
22.68
14
26.84
12.25
14.59
39.76
15
31.30
12.40
18.90
24.71
16
29.46
12.80
16.66
-100.57
17
24.97
13.25
11.72
5.13
18
30.11
13.00
17.11
20.22
19
26.9
12.72
14.18
38.39
20
24.47
13.02
11.45
9.63
21
20
12.75
7.25
19.88
Ⅲ参考文献
1、 《给水排水设计手册》(第三册 城镇给水),中国建筑工业出版社
2、 《给水排水管网系统》(第二版),中国建筑工业出版社
Ⅳ附录
附录一:
12