GLOBAL CHILLER —— 30HXC
— 1 —
The 30HXC units are water-cooled chillers, designed
from the ground up to meet the needs of today and
tomorrow:
- Ecological HFC-134a refrigerant
- Screw compressors
- Fits through a standard door with no
disassembling required
- Mechanically cleanable evaporators and
condensers
Feature
Quality design and construction make the
30HXC unit the preferred choice.
Non-controlled, ozone-benign HFC-134a
refrigerant. HFC-134a is a proven, non-toxic,
non-flammable refrigerant which will have the
highest usage of any new refrigerant.
Medium-pressure refrigerant HFC-134a
minimize stress on the compressors and ensure
their long term operating life.
The 30HXC units are equipped with screw
compressors for extremely quiet operation and
low-vibration levels.
The 30HXC units exceed the efficiency level of
average industry standards for both full-and
part-load operation, saving on operating costs,
through lower electrical power consumption.
The 30HXC control is fully automatic. The
leaving water temperature is continuously
monitored to detect load and flow changes. This
combination provides the most precise
temperature control available.
Two independent refrigerant circuits: the second
one takes over automatically, while the first one
is in the malfunctions, maintaining partial cooling
under all circumstances.
Easy installation, the 30HXC chillers are
supplied with a full refrigerant charge, and
conveniently located power supply and water
inlet and outlet connections.
Auto-diagnostics, quick display of the machine
status.
Multiple compressor concept for optimized
part-load efficiency and minimized starting
current.
Series star/delta starter, limiting the start-up
current.
Easy installation
The 30HXC has a compact design that fits
through a standard door opening and requires
minimal indoor space. The 30HXC is supplied as
a complete package for easy installation.
30HXC units have a single power point and one
main disconnect/isolator switch for size
GLOBAL CHILLER —— 30HXC
— 2 —
30HXY065A to 100A, 30HXC130A1 to 190A1,
and one power point and one main
disconnect/isolator switch per circuit for size
30HXC230A to 30HXC375A.
The hydraulic connections are simple and
facilitiated by the use of factory-supplied
evaporator and condenser short steel pipes to
be welded on site.
Simple to service
Mechanically-cleanable evaporator and
condenser.
Twin-screw compressors which require minimum
routine service and/or maintenance.
Easily accessed suction and discharge pressure
and temperature information via a display
module.
PRO-DIALOG 4 control
PRO-DIALOG 4 is an advanced numeric control
system that combines intelligence with great
operating simplicity.
PRO-DIALOG 4 ensures intelligent leaving water
temperature control and optimizes energy
requirements.
The PID control algorithm with permanent
compensation for the difference between the
heat exchanger entering and leaving
temperature, anticipates load variations,
guarantees leaving water temperature stability
and prevent unnecessary compressor cycling.
The long-stroke electronic expansion valve(EXV),
allows a significant energy efficiency
improvement at part load conditions, and
faultless chiller operation in a wider temperature
range.
Adjustable ramp loading, according to the inertia
of the application, avoids load increases that are
too fast and too frequent, increasing unit life and
limiting power consumption peaks.
Several capacity loading possibilities ensure
improved start-up at low outdoor air temperature,
and permit use of one of the refrigerant circuits
as a back-up circuit.
PRO-DIALOG 4 ensures preventive protection and
enhances chiller reliability.
Equalization of compressor operating hours.
No capillary tubes or pressure stats(except as
safety device).
PRO-DIALOG 4 monitors all chiller safety
parameters. The fault history function and the
fault codes facilitate immediate fault location.
PRO-DIALOG 4 offers extended communications
capabilities
Clear and easy-to-understand operator interface.
The LEDs, numeric displays and touch keys are
well-positioned on the schematic chiller diagram.
The user immediately knows all operating
parameters: pressures, temperatures, operating
hours, etc.
The extensive chiller remote control capabilities
(wired connection) allow integration into buiding
monitoring systems.
Optional RS485 serial port for connection to the
Carrier Comfort Network(CCN) or any other
monitoring system(optional communications
interface with open protocol allows transfer of
almost 40 parameters).
GLOBAL CHILLER —— 30HXC
— 3 —
Physical data
30HXY 30HXC Model
065A 100A 130A1 140A1 155A1 190A1 230A 260A 285A 310A 345A 375A
Net nominal cooling capacity kW 241 335 449 509 541 651 812 897 985 1106 1204 1300
Compressors Semi-hermetic, twin-screw POWER3
Quantity-Circult A 1 1 2 2 2 2 2 2 2 2 2 2
Quantity-Circult B - - - - - - 1 1 1 2 2 2
No. Of control steps 3 3 5 5 5 5 8 8 8 10 10 10
Minimum step capacity % 40 40 19 17 19 21 14 14 14 10 10 10
Evaporator Shell and tube with internally finned copper tubes
Entering water temperature ℃ 12
Leaving water temperature ℃ 7
Net water volume l 56 61 65 75 75 88 155 170 170 191 208 208
Inlet/outlet in 3.5 4 5 5 5 5 6 6 6 8 8 8
Max. water side operating
pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Condenser Shell and tube with internally finned copper tubes
Entering water temperature ℃ 30
Leaving water temperature ℃ 35
Net water volume l 61 70 78 90 90 108 190 190 190 255 255 255
Inlet/outlet in 4 5 5 5 5 6 8 8 8 8 8 8
Max. water side operating
pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Refrigerant charge HFC-134a
Circult A kg 59 83 98 96 111 140 117 117 132 109 96 119
Circult B kg - - - - - - 75 75 80 106 109 137
Dimensions
Length mm 2100 2794 3278 3278 3278 3278 3912 3912 3912 4521 4521 4521
Width mm 950 950 980 980 980 980 1015 1015 1015 1015 1015 1015
High mm 1816 1930 1816 1816 1816 1941 2060 2060 2060 2112 2112 2112
Net weight kg 1750 1950 2474 2537 2547 2983 4242 4296 4416 5014 5090 5258
Operating weight kg 1900 2110 2617 2702 2712 3179 4602 4656 4776 5477 5553 5721
Electrical data
30HXC/HXY 065A 100A 130A1 140A1 155A1 190A1 230A 260A 285A 310A 345A 375A
Power circuit
Nominal power supply V-ph-Hz 400-3-50
Voltage range V 360-440
Nominal power input* kW 52 69 90 102 112 130 164 192 196 221 251 263
Nominal current drawn* A 90 143 161 190 198 234 300 335 348 410 432 461
Max. starting current A 206 328 298 333 355 442 683 732 824 834 889 997
Standard Eurovent conditions: Evaporator entering/leaving water temperature 12℃ and 7℃. Condenser
entering/leaving water temperature 30℃/35℃. Fouling factor = 0.000044 m2 K/W.
Effective power input = power input of the compressors + the control circuit + the power input of the pump to
overcome the evaporator pressure drop.
Net cooling capacity = gross cooling capacity minus the water pump heat against the internal evaporator
pressure drop.
Short steel pipes factory-supplied, to be installed on site for evaporator and condenser water connections.
GLOBAL CHILLER —— 30HXC
— 4 —
Physical data of voltage 380V-60Hz (option 61)
30HXY 30HXC Model
065A 100A 130A1 140A1 155A1 190A1 230A 260A 285A 310A 345A 375A
Net nominal cooling capacity kW 241 332 449 509 541 644 812 897 970 1090 1195 1290
Compressors Semi-hermetic, twin-screw POWER3
Quantity-Circult A 1 1 2 2 2 2 2 2 2 2 2 2
Quantity-Circult B - - - - - - 1 1 1 2 2 2
No. of control steps 3 3 5 5 5 5 8 8 8 10 10 10
Minimum step capacity % 40 40 19 17 19 21 14 14 14 10 10 10
Evaporator Shell and tube with internally finned copper tubes
Entering water temperature ℃ 12
Leaving water temperature ℃ 7
Net water volume l 56 61 65 75 75 88 155 170 170 191 208 208
Inlet/outlet in 3.5 4 5 5 5 5 6 6 6 8 8 8
Max. water side operating
pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Condenser Shell and tube with internally finned copper tubes
Entering water temperature ℃ 30
Leaving water temperature ℃ 35
Net water volume l 61 70 78 90 90 108 190 190 190 255 255 255
Inlet/outlet in 4 5 5 5 5 6 8 8 8 8 8 8
Max. water side operating
pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Refrigerant charge HFC-134a
Circult A kg 59 83 98 96 111 140 117 117 132 109 96 119
Circult B kg - - - - - - 75 75 80 106 109 137
Dimensions
Length mm 2100 2794 3278 3278 3278 3278 3912 3912 3912 4521 4521 4521
Width mm 950 950 980 980 980 980 1015 1015 1015 1015 1015 1015
High mm 1816 1930 1816 1816 1816 1941 2060 2060 2060 2112 2112 2112
Net weight kg 1750 1950 2474 2537 2547 2983 4242 4296 4416 5014 5090 5258
Operating weight kg 1900 2110 2617 2702 2712 3179 4602 4656 4776 5477 5553 5721
Electrical data of voltage 380V - 60Hz (option 61)
30HXC/HXY 065A 100A 130A1 140A1 155A1 190A1 230A 260A 285A 310A 345A 375A
Power circuit
Nominal power supply V-ph-Hz 380-3-60
Voltage range V 342-418
Nominal power input* kW 52 68 91 103 111 129 166 189 199 224 249 262
Nominal current drawn* A 106 133 178 198 215 257 315 352 388 432 469 517
Max. starting current A 225 315 279 313 335 417 597 645 736 752 802 914
Standard Eurovent conditions: Evaporator entering/leaving water temperature 12℃ and 7℃. Condenser
entering/leaving water temperature 30℃/35℃. Fouling factor = 0.000044 m2 K/W.
Effective power input = power input of the compressors + the control circuit + the power input of the pump to
overcome the evaporator pressure drop.
Net cooling capacity = gross cooling capacity minus the water pump heat against the internal evaporator
pressure drop.
Short steel pipes factory-supplied, to be installed on site for evaporator and condenser water connections.
GLOBAL CHILLER —— 30HXC
— 5 —
Physical data of voltage 460V - 60Hz (option 60)
30HXY 30HXC Model
065A 100A 130A1 140A1 155A1 190A1 230A 260A 285A 310A 345A 375A
Net nominal cooling capacity kW 241 332 449 509 541 644 812 897 970 1090 1195 1290
Compressors Semi-hermetic, twin-screw POWER3
Quantity-Circult A 1 1 2 2 2 2 2 2 2 2 2 2
Quantity-Circult B - - - - - - 1 1 1 2 2 2
No. of control steps 3 3 5 5 5 5 8 8 8 10 10 10
Minimum step capacity % 40 40 19 17 19 21 14 14 14 10 10 10
Evaporator Shell and tube with internally finned copper tubes
Entering water temperature ℃ 12
Leaving water temperature ℃ 7
Net water volume l 56 61 65 75 75 88 155 170 170 191 208 208
Inlet/outlet in 3.5 4 5 5 5 5 6 6 6 8 8 8
Max. water side operating
pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Condenser Shell and tube with internally finned copper tubes
Entering water temperature ℃ 30
Leaving water temperature ℃ 35
Net water volume l 61 70 78 90 90 108 190 190 190 255 255 255
Inlet/outlet in 4 5 5 5 5 6 8 8 8 8 8 8
Max. water side operating
pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Refrigerant charge HFC-134a
Circult A kg 59 83 98 96 111 140 117 117 132 109 96 119
Circult B kg - - - - - - 75 75 80 106 109 137
Dimensions
Length mm 2100 2794 3278 3278 3278 3278 3912 3912 3912 4521 4521 4521
Width mm 950 950 980 980 980 980 1015 1015 1015 1015 1015 1015
High mm 1816 1930 1816 1816 1816 1941 2060 2060 2060 2112 2112 2112
Net weight kg 1750 1950 2474 2537 2547 2983 4242 4296 4416 5014 5090 5258
Operating weight kg 1900 2110 2617 2702 2712 3179 4602 4656 4776 5477 5553 5721
Electrical data of voltage 460V – 60Hz (option 60)
30HXY/HXC 065A 100A 130A1 140A1 155A1 190A1 230A 260A 285A 310A 345A 375A
Power circuit
Nominal power supply V-ph-Hz 460-3-60
Voltage range V 414-506
Nominal power input* kW 52 68 91 103 111 129 166 189 198 223 249 262
Nominal current drawn* A 90 107 147 164 178 213 260 291 319 355 388 425
Max. starting current A 205 285 244 274 292 363 521 560 639 648 690 786
Standard Eurovent conditions: Evaporator entering/leaving water temperature 12℃ and 7℃. Condenser
entering/leaving water temperature 30℃/35℃. Fouling factor = 0.000044 m2 K/W.
Effective power input = power input of the compressors + the control circuit + the power input of the pump to
overcome the evaporator pressure drop.
Net cooling capacity = gross cooling capacity minus the water pump heat against the internal evaporator
pressure drop.
Short steel pipes factory-supplied, to be installed on site for evaporator and condenser water connections.
GLOBAL CHILLER —— 30HXC
— 6 —
Dimensions/clearances
30HXY 065A
70
0
1760 F
50
0
10
09
50 90
0 1
00
25
58
8
326
950
330 1434
2194
D
C
B
A
1000
E
180
10
0
①Required clearances for maintenance
②Recommended space for tube removal (clearance 1760 and 1000 can be either on the right or
the left side).
Water outlet Water inlet Power supply
GLOBAL CHILLER —— 30HXC
— 7 —
30HXY 100A
70
0
2360 F
50
0
10
09
50 90
0 1
00
25
58
8
326
950
593 1600
2794
D
C
B
A
1000
E
180
10
0
③Required clearances for maintenance
④Recommended space for tube removal (clearance 2360 and 1000 can be either on the right or
the left side).
Water outlet Water inlet Power supply
GLOBAL CHILLER —— 30HXC
— 8 —
30HXC 130A1-190A1
2990 689
70
0
1000
50
0
98
0
25
93
0 1
00
10
0
58
8
C
B
A
F 1828
3250
E
180
980
D
326
10
0
8-Φ22
⑤Required clearances for maintenance
⑥Recommended space for tube removal (clearance 2990 and 1000 can be either on the right or
the left side).
Water outlet Water inlet Power supply
GLOBAL CHILLER —— 30HXC
— 9 —
30HXC 230A-285A
AB
BA
①Required clearances for maintenance
②Recommended space for tube removal (clearance 3600 and 1000 can be either on the right or
the left side).
Water inlet Water outlet Power supply
GLOBAL CHILLER —— 30HXC
— 10 —
30HXC 310A-375A
AB
BA
①Required clearances for maintenance
②Recommended space for tube removal (clearance 4200 and 1000 can be either on the right or
the left side).
Water inlet Water outlet Power supply
GLOBAL CHILLER —— 30HXC
— 11 —
CHILLER FOOTPRINT
Field Wiring
Spare Safety Port
Remote Cooling/Heating Control
Demand Limit
Dual Setpoint
Reset Setpoint
Alarm Circuit A
Alarm Circuit B
Remote ON/OFF
CCN Communication Bus
Machine figure dimension,basement need additional clearance.
Section F-F
Install Hole 100×100
Dimension(mm) A B C P Q R
30HXY065A 330 1434 2194 900 100 950
30HXY100A 560 1600 2794 900 100 950
30HXC130A1
30HXC140A1
30HXC155A1
30HXC190A1
685 1828 3278 930 100 980
30HXC230A
30HXC260A
30HXC285A
1092 1785 3912 965 100 1015
30HXC310A
30HXC345A
30HXC375A
1399 1659 4521 965 100 1015
Load(kg) 1 2 3 4 1’ 2’ 3’ 4’ Operating Weight‚
30HXY065A 657 448 473 322 687 418 494 301 1900
30HXY100A 607 456 596 451 625 478 574 433 2110
30HXC130A1 812 549 749 507 848 512 782 475 2617
30HXC140A1 840 567 774 523 876 530 808 488 2702
30HXC155A1 842 569 776 525 880 532 810 490 2712
30HXC190A1 987 667 910 615 1030 623 950 576 3179
30HXC230A 1348 958 1342 954 1399 907 1393 903 4602
30HXC260A 1364 970 1358 964 1415 918 1408 915 4656
30HXC285A 1399 995 1392 990 1452 942 1445 937 4776
30HXC310A 1786 1303 1381 1007 1850 1239 1430 958 5477
30HXC345A 1811 1321 1400 1021 1875 1256 1450 972 5553
30HXC375A 1865 1361 1443 1052 1931 1295 1494 1001 5721
GLOBAL CHILLER —— 30HXC
— 12 —
Standard Accessories
Item Description Quantity
a Flow monitor switch for evaporator 1
b M20×300 hex screw 4
c Handle of disconnect switch 2
d Couplings 4
e Short steel pipes 4
Main Options
Option Description Remark
104 Condenser and evaporator maximum water-side operating pressure of 16 bar
107E Reversed evaporator water inlet/outlet
104A16 Condenser and evaporator maximum water-side operating pressure of 21 bar
107C Reversed condenser water inlet/outlet
Acc3 RS485 communications interface with open protocol
25A Compressor soft start electronic starter
5 Brine unit for leaving brine < +4。C to > -6。C
150A Water-to-water heat pump Condenser leaving water > 47
。C to <
60。C
150 High condensing temperature unit and non-reversible heat pump
Condenser leaving water > 40。C to <
47。C
本文档为【30HXC English catalog (一冷开利出口)】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。