IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 2, APRIL 2008 657
Overvoltage Protection of Large Power
Transformers—A Real-Life Study Case
Claus Leth Bak, Kristin Erla Einarsdóttir, Einar Andresson, Jesper M. Rasmussen, Jan Lykkegaard, and
Wojciech Wiechowski
Abstract—This paper demonstrates the results from a detailed
study of the overvoltage protection of a particular 400/150-kV
400-MVA power transformer. The work presented here is based on
a real-life power system substation design and data and initiated
by Danish TSO Energinet.dk as a consequence of serious trans-
former overvoltage damage. A simulation model for the entire
system consisting of overhead line, transformer, surge arrester,
and earth grid has been created in PSCAD/EMTDC. The main
focus has been put on the earth grid, which has been submodeled
in detail in MATLAB using an electromagnetic transient approach
based on the thin-wire program made by J. H. Richmond for
NASA in 1974. The earth grid model is verified with excellent
agreement compared to already published results. The overvoltage
performance of the particular case is analyzed, and it shows that
the transformers LIWL have probably been exceeded. It is clearly
illustrated that the transient performance of the earth grid plays
an important role in the overall overvoltage protection system
design.
Index Terms—Dynamic resistance, earth grid design, light-
ning impulse withstand level (LIWL), MATLAB, overvoltage
protection, overvoltage protection simulation, PSCAD/EMTDC,
transient behavior.
I. INTRODUCTION
ON June 18, 2002, a heavy thunderstorm swept over NorthJutland, Denmark, resulting in a serious fault in Energinet.
dk’s 400/150-kV transformer placed at the Nordjyllandsværket
400-kV transformer station (NVV5).
According to Energinet.dk, the fault was caused by a light-
ning transient on the 150-kV transmission grid.
Apparently, the transient lightning voltage exceeded the
LIWL of the transformer.
Fig. 1 illustrates the record breaking amount of lightning over
Denmark on June 18, 2002.
Manuscript received September 6, 2006; revised February 5, 2007. Paper no.
TPWRD-00522-2006.
C. L. Bak is with the Institute of Energy Technology (IET), Aalborg Univer-
sity, Aalborg East DK-9220, Denmark (e-mail: clb@iet.aau.dk).
K. E. Einarsdóttir is with Rafhönnun, Reykjavik 108, Iceland..
E. Andresson is with RTS Electrical Engineering Consultants, Reydarfjordur
730, Iceland.
J. M. Rasmussen is with Aalborg Kommune Elforsyningen, AKE, Aalborg
9000, Denmark.
J. Lykkegaard and W. Wiechowski are with Energinet.dk (TSO), Frederica
7000, Denmark.
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TPWRD.2007.905793
Fig. 1. Intensity of lightnings over Denmark on June 18, 2002.
This incident has caused speculations within Energinet.dk
about the effectiveness of the lightning protection of the trans-
formers now used at Energinet.dk’s power stations. The possi-
bility of this occurring again to any of the other power trans-
formers in Eltra’s possession is a major concern. The main con-
cern of the project is to make a simulation model of that part
of the substation which surrounds the transformer (see Fig. 2),
and to simulate a double exponential lightning impulse current
directly on a phase line, which will propagate toward the trans-
former in the form of a travelling wave. The main emphasis will
be put on investigating the overvoltage distribution in the system
with respect to the LIWL of the transformer and to simulate the
components that are most likely to have caused excessive LIWL,
thereby damaging the transformer. These are the 150-kV surge
arresters, the earth grid with respect to GPR, and the transformer
itself. The 150-kV overhead line between the 150-kV substation
NVV3 and the 400-kV substation NVV5 is included in the sim-
ulation. The results will then be used to determine a possible
weakness in the overall overvoltage protection design.
This paper presents a description of the real-life power system
with sufficient details to study the overvoltage protection of
the power transformer in detail and a description of the trans-
former damage. A number of causes capable of resulting in such
damage is listed and a hypothesis is postulated.
Hypothesis: The transformer was not adequately protected
at the 150-kV side, so the lightning insulation withstand level
(LIWL) was exceeded.
The action of this hypothesis was to model the system (Fig. 2)
in such detail that a realistic simulation of the overvoltage pro-
tection behavior could be performed and, in this way, spread
0885-8977/$25.00 © 2007 IEEE
658 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 2, APRIL 2008
Fig. 2. Overview of the system, with the overhead line, the surge arrester, the
transformer, and the earth grid.
Fig. 3. Photograph of the 400/150-kV power transformer and its nearest sur-
roundings at the 400-kV substation NVV5.
some light on the possible cause of transformer damage. The
simulation model is further used to analyze possible improve-
ments of the overvoltage protection, mainly regarding the de-
sign of the earth grid. This will be presented in another paper.
II. SYSTEM DESCRIPTION
A. Substation
The damaged power transformer is located at a normal out-
door switchyard with proper shielding of both 150- and 400-kV
overhead line connections plus grounding systems and rods at
the entire substation area. Fig. 3 shows a photograph of the trans-
former location at the substation.
Fig. 4 shows the configuration in a scalable drawing so the
connection of surge arresters and shielding can be identified:
1) LV surge arrester, 2) HV surge arrester, 3) transformer, 4)
coolers, 5) suspension tower, 6) insulator, 7) ground wires, 8)
HV phase conductor, and 9) LV phase conductor. Further details
can be found in [1] which is a Masters Thesis elaborated by K.
E. Einarsdottir, E. Andresson, and J. M. Rasmussen. This paper
presents the main results of parts of their work.
B. 400/150-kV Transformer
The transformer is a three-phase 400-MVA ASEA oil-im-
mersed autotransformer with data according to Table I.
Bushings have a higher LIWL than transformers (LV side 750
kV and HV side 1675 kV). The transformer age is 14 years.
Fig. 4. Configuration of transformer installation.
TABLE I
400/150-kV ASEA AUTOTRANSFORMER DATA
TABLE II
150-kV SURGE ARRESTER DATA
Prehistory: Inservice always and very lightly loaded. Oil and
gas analysis has previously shown no sign of premature aging.
C. Surge Arresters
Only the 150-kV surge arrester data are listed (as the over-
voltage is assumed to originate from the LV side). These are
ASEA XAR 170-A3 with data according to Table II and a pro-
tective characteristic according to Fig. 5.
D. Earth Grid
The surge arresters are connected to the same earth system
as the power transformer, although no direct connection be-
tween surge arrester ground terminal and transformer exists,
which is recommended in certain literature (i.e., [2] and trans-
former manufacturer ABB). The earth grid is a slightly irreg-
ular meshed grid of approximately 140 135 m or about 19
000 m in size. It is made of 95 m bare stranded copper wires
and is buried at a depth of approximately 1 m. Earth rods are
BAK et al.: OVERVOLTAGE PROTECTION OF LARGE POWER TRANSFORMERS 659
Fig. 5. ASEA XAR 170-A3 surge arrester data.
Fig. 6. Earth grid in the surrounding of the transformer. The 150-kV connection
is toward the top of the figure. Figure scalable with coordinates shown to the left.
Figure shows only part of the earth grid.
located at the periphery of the earth grid at an 8–42-m distance
from each other. These are of the type Elpress, each consisting
of a 6-m-long steel pipe and a 95-mm copper wire and located
at a minimum of 1 m from each foundation as required by the
IEC-1024-1 standard [3]. Fig. 6 shows that the transformer and
the surge arresters are positioned at the outskirts of the earth
grid, with the 150-kV surge arresters located only 8 m from the
periphery. The squares and irregular boxes are the equipment
foundation blocks. All three surge arresters are interconnected
forming a relatively large mesh size to the periphery of 21
7.5 m and a mesh size of 4 16 m toward the transformer. The
surge arresters are connected to the transformer neutral point as
may be seen in Fig. 6, with a conductor length of 15 m from the
phase A surge arrester, grid depth included. No earth rods are
located very close to the surge arresters.
The transformer is mounted on support units over a well that
will drain any oil spill from the transformer. According to En-
erginet.dk, gravel may have been used as a fill up material when
mounting the transformer and the surge arresters. This gravel
may therefore embrace the earth conductors between the trans-
former and the surge arresters. The dynamic behavior of the
earth system with respect to lightning impulses is the main focus
of this project and is described in Section III. The static resis-
tance of the entire earth grid is calculated based on the Schwartz
Fig. 7. Damaged transformer. (a) The three phases with the faulty phase fur-
thest to the left. (b) The faulty winding seen from the outside after various paper
layers have been removed.
Fig. 8. (a) Electrical diagram showing where the fault has occurred and (b) the
fault occurring between two layers in the series winding.
equation from IEEE-80 [4] and amounts to
with specific resistivity of the soil .
E. Transformer Damage
The lightning activity in Denmark on June 18, 2002 was very
heavy. There were more than 110 000 lightnings over Denmark
that day and over 10 000 lightnings in an area with a radius of 50
km around the transformer substation. About 8500 positive and
negative sky-to-earth lightnings were registered and 4%–5% of
these had an amplitude of more than 30 kA and nearly all were
negative (99%). Some of these were located (taking the accuracy
of lightning detection systems into consideration) very close to
the overhead lines of the substation. Fig. 7. shows the damage
after opening the transformer at the ABB factory. The trans-
former winding connection (autotransformer) is shown in Fig. 8,
where it is seen that the fault occurred between two layers of
the series winding. After disassembling, the transformer was re-
paired and put back into service after approximately one year.
III. MODELLING AND SIMULATION
In order to simulate the overvoltage amplitude at the trans-
former terminals, models are created from a transformer, surge
arrester, earth grid, and overhead line. These are combined in a
model of the total system implemented in the PSCAD/EMTDC
software together with a double-exponential lightning surge
source. The models of each component will be discussed briefly
in the following sections. Further explanations to the models,
especially concerning the earth grid model, can be found in [1]
and is intended to be the main topic of a future paper.
A. ASEA Autotransformer Model
The transformer must be modeled sufficiently to possess
terminal properties, which reflects its high-frequency behavior
660 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 2, APRIL 2008
Fig. 9. Transformer winding with one end grounded. (a) l is the total length of
the winding and x is the distance from the top of the winding to an arbitrary
point in the winding. (b) Equivalent electrical circuit of the winding [6].
Fig. 10. Capacitance values for the autotransformer windings (ABB).
sufficiently to achieve realistic results of overvoltage stresses.
Transformers are normally modeled [5] as a single capacitance
from line terminal to ground. More detailed models are nor-
mally used for studying the internal voltage distribution of the
windings. This work uses an approach originally proposed by
[6], which represents each phase winding as one single winding
possessing capacitive, inductive, and resistive behavior as
illustrated in Fig. 9.
Depending on available transformer construction data and the
need for a very precise model, the concept in Fig. 9 can be less
or more complex (i.e., the degree of “lumpedness” and the in-
clusion of self- and mutual (between parts of the winding) in-
ductances and resistive damping). This work has used a combi-
nation of capacitances (originating from ABB data, see Fig. 10)
and resistances and inductances calculated on a simplified rep-
resentation of the transformer geometry.
The main purpose of extending the transformer model to in-
clude both inductance and resistance was chosen in order to
verify the high-frequency terminal behavior of the transformer,
as this is very important for reliable results in the complete
model. This was accomplished by implementing the model [1]
in PSCAD and simulating the same situation as the transformer
is tested against it in the factory test. This is the Hagenguth test
Fig. 11. Model proposed by Fernandez.
Fig. 12. Surge arrester model and double exponential test circuit in PSCAD.
[7, p. 165], which impresses reduced, full, and chopped light-
ning impulse voltages to the transformer terminals and measures
the ground return current to check for damages that occurred
during the testing. The factory test was available for the present
transformer and this approach was carried out with satisfactory
results [1], which supported the belief of a sufficient model of
the transformer, although it is quite complicated to obtain results
with more than just the main features (rise time, peak value, and
decaying) of the ground return current close to the actual test
results. This model consists of 63 partial lumped capacitances,
26 lumped inductances (air core assumed concerning high-fre-
quency behavior), and 26 resistances for each phase.
B. ZnO Surge Arrester
The nonlinear surge arrester dynamics are modeled using the
approach proposed by [8], which is a simplified model of the
IEEE model with model parameters described as proposed in
[9] and [10]. Fig. 11 shows the Fernandez approach.
represents the inductance in the electric path through the
ZnO blocks and is determined using the dimensions of the surge
arrester.
and represent the nonlinear resistivity of the ZnO
blocks and can be estimated from the surge arrester residual
voltage, see Section II-C.
represents the terminal capacitance of the surge arrester.
R is included to avoid numerical instability.
The surge arrester model (see Fig. 12) is verified against
manufacturer residual voltage data and excellent agreement
was achieved (maximum 1.5% error).
BAK et al.: OVERVOLTAGE PROTECTION OF LARGE POWER TRANSFORMERS 661
C. Earth Grid
The purpose of making a model of the earth system is to cal-
culate the voltage between the surge arrester ground terminal
and the neutral point of the transformer, which results from a
difference in ground potential rise (GPR) under the two com-
ponents, when a lightning current surges through the surge ar-
rester into the earth grid. An electromagnetic-field approach is
the best choice when the need for calculation of transient volt-
ages between points of the earth grid is present [11]. The earth
grid model is a transient electromagnetic program written in the
C-based programming language of MATLAB. It is based on the
thin-wire structure program originally written in Fortran code
by J. H. Richmond [12], [13]. The model performs an electro-
magnetic analysis on wire structures in the complex frequency
domain, based on closed-form expressions and Simpson’s rule
of integration for the solution of electromagnetic fields. Its func-
tion is to determine the electric near fields at the surface of the
wire structure, due to the longitudinal current flowing in each
section of the wire. The electric-field calculation is then used
to determine the dynamic impedance, both self and mutual, of
the wire structure in order to determine the current distribution
in the overall grid. The grid is divided into segments and the
current distribution is approximated by defining every two seg-
ments as a dipole with a piecewise sinusoidal current distribu-
tion given with sinusoidal expansion functions, as it is very close
to the natural current distribution on a perfectly conducting thin
wire. A sinusoidal dipole is used as a test source, as this is prob-
ably the only finite-line source with simple closed-form expres-
sions for the near-zone fields, and the mutual impedances be-
tween two sinusoidal dipoles may be determined from exponen-
tial integrals [13, p. 7]. The thin-wire approach has been used
by Grcev [11], [14]–[17] to determine the electric fields in earth
grids caused by lightning surge currents. Grcev refers to Rich-
mond’s thin wire program in [15, p. 394], but he additionally in-
cludes image theory in his model to account for reflections due
to interface of air and earth, as this is not included in Richmond’s
program. Grcev also describes in his articles how to implement
an injected current, also not included in Richmond’s program.
As Richmond’s thin-wire program was not specifically designed
for calculating electromagnetic fields in earth grids, the program
needed to be adapted to the problem presented in this report.
All unnecessary functions to the presented problem have been
eliminated from the program, which now has the main function
of calculating antenna problems in a homogeneous conducting
medium. Reflections of the electric field due to the interface of
air and earth have been taken into consideration with the mod-
ified image theory, and to make injection of surge current pos-
sible, the modifications suggested by Grcev have been imple-
mented in the program. Only the front time of the current wave is
of interest since this provides the highest frequency and thereby
the highest electric fields. All simulations are therefore made
in the frequency domain, using the frequency corresponding to
the desired current front time at each time, and a conversion
of the current wave from the time domain to the frequency do-
main by Fourier transforms is therefore not needed. The basic
model (before implementing modified image theory and injec-
tion current) has been verified thoroughly with results presented
Fig. 13. Linear electrode energized at one of the ends.
in Richmond’s notes [12]. After implementation of the modified
image theory and the injection current, the model was verified
by comparing the results with the results presented in [15] with
very good agreement. The following assumptions and limita-
tions are made in the model of the earth grid.
1) The wire structure is made of straight cylindrical metallic
conductors.
2) The wire is subject to the thin-wire approximation, and the
conductor radius is therefore assumed to be much smaller
than the wavelength, with the wire length being much
greater than the wire radius (At least 30 times greater [12,
p. 12]).
3) Image theory is applied to compensate for the effects of
a ground plane (i.e., the interface between air and earth is
taken into consideration). This limits the frequency range
of the model to a few megahertz [16].
4) The media of earth and air are assumed to be homogeneous
with a horizontal ground plane boundary between them.
5) The current on wire ends is assumed to be zero.
6) For accuracy, the longest wire segment should not greatly
exceed 1/4 wavelength [13].
7) Soil ionization is not taken into consideration.
The MATLAB-made program is called TEMP and details can
be found in [1] and a future paper. Verification is performed
against two situations:
1) 15-m-long Horizontal Electrode: According to [15], ver-
ification is carried out against a 15-m-long horizontal electrode
(Fig. 13) buried at 1-m depth (soil resistivity 2000 m) with a
wire radius of 0.007 m with energization by injecting time-har-
monic currents of 1 A at three different frequencies: 50 Hz,
2.247 MHz, and 6.741 MHz.
Results from TEMP are compare
本文档为【过电压保护】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。