DESIGN DETAIL
TD_SX440 AVR_03.05_03_GB
SX440 AUTOMATIC VOLTAGE
REGULATOR (AVR)
SPECIFICATION, INSTALLATION AND ADJUSTMENTS
General description Technical specification
SX440 is a half-wave phase-controlled thyristor type
Automatic Voltage Regulator (AVR) and forms part of the
excitation system for a brush-less generator.
In addition to regulating the generator voltage, the AVR
circuitry includes under-speed and sensing loss
protection features. Excitation power is derived directly
from the generator terminals.
Positive voltage build up from residual levels is ensured
by the use of efficient semiconductors in the power
circuitry of the AVR.
The AVR is linked with the main stator windings and the
exciter field windings to provide closed loop control of the
output voltage with load regulation of +/- 1.0%.
In addition to being powered from the main stator, the
AVR also derives a sample voltage from the output
windings for voltage control purposes. In response to this
sample voltage, the AVR controls the power fed to the
exciter field, and hence the main field, to maintain the
machine output voltage within the specified limits,
compensating for load, speed, temperature and power
factor of the generator.
A frequency measuring circuit continually monitors the
generator output and provides output under-speed
protection of the excitation system, by reducing the output
voltage proportionally with speed below a pre-settable
threshold. A manual adjustment is provided for factory
setting of the under frequency roll off point, (UFRO). This
can easily be changed to 50 or 60 Hz in the field by push-
on link selection.
Provision is made for the connection of a remote voltage
trimmer, allowing the user fine control of the generator's
output.
An analogue input is provided allowing connection to a
Newage Power Factor controller or other external devices
with compatible output.
The AVR has the facility for droop CT connection, to allow
parallel running with other similarly equipped generators.
INPUT
Voltage 190-264V ac
Frequency 50-60 Hz nominal
Phase 1
Wire 2
OUTPUT
Voltage max 90V dc at 207V ac input
Current continuous 4A dc
Intermittent 6A for 10 secs
Resistance 15 ohms minimum
REGULATION
+/- 1% (see note 1)
THERMAL DRIFT
0.04% per deg. C change in AVR ambient (note 2)
TYPICAL SYSTEM RESPONSE
AVR response 20ms
Filed current to 90% 80 ms
Machine Volts to 97% 300ms
EXTERNAL VOLTAGE ADJUSTMENT
+/-10% with 1 k ohm 1 watt trimmer (see note 3)
UNDER FREQUENCY PROTECTION
Set point 95% Hz (see note 4)
Slope 170% down to 30 Hz
UNIT POWER DISSIPATION
12 watts maximum
BUILD UP VOLTAGE
4 Volts @ AVR terminals
ANALOGUE INPUT
Maximum input +/- 5V dc (see note 5)
Sensitivity 1v for 5% Generator Volts (adjustable)
Input resistance 1k ohm
QUADRATURE DROOP INPUT
10 ohms burden
Max. sensitivity: 0.07 A for 5% droop 0PF
Max. input: 0.33A
ENVIRONMENTAL
Vibration 20-100 Hz 50mm/sec
100Hz – 2kHz 3.3g
Operating temperature -40 to +70 oC
Relative Humidity 0-70 oC 95% (see note 6)
Storage temperature -55 to +80 oC
NOTES
1. With 4% engine governing.
2. After 10 minutes.
3. Applies to Mod status S onwards. Generator de-rate
may apply. Check with factory.
4. Factory set, semi-sealed, jumper selectable.
5. Any device connected to the analogue input must be
fully floating (galvanically isolated from ground), with an
insulation strength of 500V ac.
6. Non condensing.
ww
w.
we
llf
ut
.co
m
DESIGN DETAIL
TD_SX440 AVR_03.06_03_GB
The main functions of the AVR are:
Potential Divider and Rectifier takes a proportion of the
generator output voltage and attenuates it. The potential
divider is adjustable by the AVR Volts potentiometer and
external hand trimmer (when fitted). The output from the
droop CT is also added to this signal. An isolating
transformer is included allowing connection to various
winding configurations. A rectifier converts the a.c. input
signal into d.c. for further processing.
The Sensing Loss Detector is an electronic changeover
switch, which normally connects the Amplifier (Amp) to
the Voltage Sensing input and automatically changes
over to the Power input when the normal sensing voltage
is lost.
The DC Mixer adds the Analogue input signal the
Sensing signal.
The Amplifier (Amp) compares the sensing voltage to the
Reference Voltage and amplifies the difference (error) to
provide a controlling signal for the power devices. The
Ramp Generator and Level Detector and Driver infinitely
control the conduction period of the Power Control
Devices and hence provides the excitation system with
the required power to maintain the generator voltage
within specified limits.
The Stability Circuit provides adjustable negative ac
feedback to ensure good steady state and transient
performance of the control system.
The Low Hz Detector measures the period of each
electrical cycle and causes the reference voltage to
be reduced approximately linearly with speed below
a presettable threshold. A Light Emitting Diode gives
indication of underspeed running.
The Synchronising circuit is used to keep the Ramp
Generator and Low Hz Detector locked to the
generator waveform period.
The Low Pass Filter prevents distorted waveforms
affecting the operation of the AVR control circiut
Power Control Devices vary the amount of exciter
field current in response to the error signal produced
by the Amplifier.
Suppression components are included to prevent
sub cycle voltage spikes damaging the AVR
components and also to reduce the amount of
conducted noise on the generator terminals..
The Power Supply provides the required voltages
for the AVR circuitry.
Suppression
Low Pass
Filter
Synchronising
Circuit
Low Hz
Detection
Power
Control
Devices
Level
Detector &
Driver
Reference
Voltage
Stability
Circuit
Potential
Divider &
Rectifier
Power
supply
Ramp
Generator
Generator
Amp
Voltage
Sensing
Hand
Trimmer
Exciter
Field
DC
Mixer
Analogue
Input
Sensing
Loss
Detector
Droop
ww
w.
we
llf
ut
.co
m
FITTING AND OPERATING
TD_SX440 AVR _03.06_03_GB
SUMMARY OF AVR CONTROLS
CONTROL FUNCTION DIRECTION
VOLTS TO ADJUST GENERATOR OUTPUT VOLTAGE CLOCKWISE INCREASES OUTPUT VOLTAGE
STABILITY TO PREVENT VOLTAGE HUNTING CLOCKWISE INCREASE THE DAMPING EFFECT
UFRO TO SET THE UFRO KNEE POINT CLOCKWISE REDUCES THE KNEE POINT
FREQUENCY
DROOP TO SET THE GENERATOR DROOP TO 5% AT 0PF CLOCKWISE INCREASES THE DROOP
VTRIM TO OPTIMISE ANALOGUE INPUT SENSITIVITY CLOCKWISE INCREASES THE GAIN OR SENSITIVITY
ADJUSTMENT OF AVR CONTROLS
VOLTAGE ADJUSTMENT
The generator output voltage is set at the factory, but can
be altered by careful adjustment of the VOLTS control on
the AVR board, or by the external hand trimmer if fitted.
Terminals 1 and 2 on the AVR will be fitted with a shorting
link if no hand trimmer is required.
CAUTION Do not increase the voltage above the rated
generator voltage. If in doubt, refer to the rating plate
mounted on the generator case.
CAUTION Do not ground any of the hand trimmer
terminals as these could be above earth potential. Failure
to observe this could cause equipment damage.
If a replacement AVR has been fitted or re-setting of the
VOLTS adjustment is required, proceed as follows:
CAUTION
1. Before running generator, turn the VOLTS control
fully anti-clockwise.
2. Turn remote volts trimmer (if fitted) to midway
position.
3. Turn STABILITY control to midway position.
4. Connect a suitable voltmeter (0-300V ac) across
line to neutral of the generator.
5. Start generator set, and run on no load at nominal
frequency e.g. 50-53Hz or 60-63Hz.
6. If the red Light Emitting Diode (LED) is illuminated,
refer to the Under Frequency Roll Off (UFRO)
adjustment.
7. Carefully turn VOLTS control clockwise until rated
voltage is reached.
8. If instability is present at rated voltage, refer to
stability adjustment, then re-adjust voltage if
necessary.
9. Voltage adjustment is now completed.
K1 K2 P2 P3 P4 XX X 3 2 2 1
A1
A2
S1
S2
1
2
3
4
5
6
7
8
C B A 50 C 60
SX440
Trim
Droop
Volts
Stability
Selection
UFRO
Frequency
Selection
Indicator
LED
Stability
K1-K2
Power isolation link
(normally fitted)
Sensing
links
standard
positions
60Hz
50Hz
< 90kW
90-550kW
> 550kW
Note. If replacing an existing SX440, position the
links and connections the same as the original
SX440.
If up grading to an SX440 refer to generator wiring
diagram for connection details.
Note. There are two terminals marked ‘2’
they are connected, either one or both can
be used.
Warning: Electrical shock can cause injury or death.
Ensure that all personnel operating, servicing,
maintaining or working near this equipment are fully
aware of the emergency procedures in case of accidents.
Before removing the protective covers to carry out
service maintenance or repair, ensure that the engine is
inhibited and the generator is electrically isolated.
ww
w.
we
llf
ut
.co
m
FITTING AND OPERATING
TD_SX440 AVR_03.06_04_GB
Barnack Road • Stamford • Lincolnshire • PE9 2NB
Tel: 00 44 (0)1780 484000 • Fax: 00 44 (0)1780 484100 © 2006 Cummins Generator Technologies
Limited.
Printed in England.
STABILITY ADJUSTMENT
The AVR includes a stability or damping circuit to provide
good steady state and transient performance of the
generator.
The correct setting can be found by running the generator
at no load and slowly turning the stability control anti-
clockwise until the generator voltage starts to become
unstable.
The optimum or critically damped position is slightly
clockwise from this point (i.e. where the machine volts are
stable but close to the unstable region).
OPTIMUM RESPONSE SELECTION
The stability selection ‘jumper’ should be correctly linked,
A-B, B-C or A-C at the bottom of the board for the frame
size of the generator, (see drawing).
UNDER FREQUENCY ROLL OFF (UFRO)
ADJUSTMENT
The AVR incorporates an underspeed protection circuit
which gives a volts/Hz characteristic when the generator
speed falls below a presettable threshold known as the
"knee" point.
The red Light Emitting Diode (LED) gives indication that
the UFRO circuit is operating.
The UFRO adjustment is preset and sealed and only
requires the selection of 50 / 60Hz using the jumper link.
For optimum setting, the LED should illuminate as the
frequency falls just below nominal, i.e. 47Hz on a 50Hz
system or 57Hz on a 60Hz system.
DROOP ADJUSTMENT
Generators intended for parallel operation are fitted with a
quadrature droop C.T. which provides a power factor
dependent signal for the AVR. The C.T. is connected to
S1, S2 on the AVR.
The DROOP adjustment is normally preset in the works
to give 5% voltage droop at full load zero power factor.
Clockwise increases the amount of C.T. signal injected
into the AVR and increases the droop with lagging power
factor (cos Ø). With the control fully anti-clockwise there
is no droop.
TRIM ADJUSTMENT
An analogue input (A1 A2) is provided to connect to the
Newage Power Factor Controller or other devices. It is
designed to accept dc signals up to +/- 5 volts.
CAUTION Any devices connected to this input must be
fully floating and galvanically isolated from ground, with
an insulation capability of 500 Vac. Failure to observe
this could result in equipment damage.
The dc signal applied to this input adds to the AVR
sensing circuit. A1 is connected to the AVR 0 volts.
Positive on A2 increases excitation. Negative on A2
decreases excitation.
The TRIM control allows the user to adjust the
sensitivity of the input. With TRIM fully anti-clockwise
the externally applied signal has no effect. Clockwise it
has maximum effect.
Normal setting is fully clockwise when used with a
Newage Power Factor Controller.
Skill requirements of personnel
Service and maintenance procedures should only
be carried out by experienced, qualified,
engineers/technicians, familiar with the
procedures and the equipment.
Before any intrusive procedures are carried out,
ensure that the engine is inhibited and the
generator is electrically isolated.
ww
w.
we
llf
ut
.co
m
本文档为【SX440,STAMFORD,调压板英文说明书】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。