Specifications are subject to change without notice (11.01.07) 1
Description & Mode of operation:
Multifunction
Multi-voltage timer with 7 knob-selectable functions and 7
knob-selectable time ranges within 0.1s and 100h. For
mounting on DIN-rail. Housing 17.5 mm wide suitable both
for back and front panel mounting.
Wide power supply range: 12 to 240 VAC/DC.
Function Op - Delay on operate
The time period begins as soon as the trigger contact is
closed.
At the end of the set delay time the relay operates and does
not release until the trigger contact is closed again or the
power supply is disconnected. If the trigger contact is
closed before the end of the delay time, the device resets
and a new time period starts.
Function In - Interval
The relay operates and the time period begins as soon as the
trigger contact is closed. The relay releases at the end of this
period or when the power supply is disconnected. The relay
operates again when the trigger contact is closed again. If the
trigger contact is closed before the end of the delay time, the
device resets and a new time period starts.
Function Io - Interval on trigger open
The relay operates and the time period begins as soon as
the trigger contact is opened. At the end of the set delay or
when the power supply is disconnected the relay releases.
The relay operates again when the trigger contact is opened
again. If the trigger contact is opened before the end of the
delay time the relay keeps ON and a new time period
begins.
Function Id - Double interval
The relay operates and the time period begins as soon as
the trigger contact is closed. The relay releases at the end of
this period or when the power supply is disconnected.
When the trigger contact is opened the relay operates again
for the set delay period. If the trigger contact is opened
before the end of the first time period the second one
begins; if the trigger contact is closed before the end of the
second time period the device resets and the first time peri-
od begins again.
FEATURES
• Selectable time range 0.1 s to 100 h
• 7 knob selectable functions:
Op - delay on operate
In - interval
Io - interval on trigger open
Id - double interval
Dr - delay on release
R - symmetrical recycler ON first
Rb - symmetrical recycler OFF first
• Automatic or manual start
• Repeatability: ≤ 0.2%
• Output: 5 A SPDT relay
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 17.5 mm DIN-rail housing
• Combined AC and DC power supply
• LED indication for relay status and power supply ON
Timer Type VIMT51CW24
Timers
Function Dr - Delay on release
The relay operates as soon as the trigger contact is closed.
The time period begins when the trigger contact is opened.
The relay releases at the end of the set delay time or when
the power supply is disconnected. The relay operates again
when the input contact is closed again. If it is opened
before the end of the delay time the relay keeps ON, a new
time period begins as soon as the contact is closed again.
Function R - Symmetrical recycler, ON-time period first
The relay operates and the time period begins as soon as
the input contact is closed. After the set delay period the
relay releases for the same time period. This sequence con-
tinues with equal ON- and OFF-time periods until the power
supply is interrupted.
Function Rb - Symmetrical recycler, OFF-time period first
The time period begins as soon as the input contact is
closed. The relay is OFF during the set delay period, after
this time it operates for the same time period. This
sequence continues with equal OFF- and ON-time periods
until the power supply is interrupted.
Additional Load
It's possible to wire an additional load (i.e. a relay) between
pins Y1 and A2, driven by the trigger contact without dam-
aging the device.
Yellow LED working mode
Timing: Slow blinking
Relay ON: See operation diagrams
Incorrect knobs position: Fast blinking
QQ
:2
49
76
31
99
1
2 Specifications are subject to change without notice (11.01.08)
VIMT51
Power ON delay ≤ 100 ms
Indication for
Power supply ON LED, green
Output relays ON LED, yellow
(flashing when timing)
Environment (EN 60529)
Degree of protection IP 20
Pollution degree 2 (IEC 60664)
Operating temperature -20° to +60°C, R.H. < 95%
Storage temperature -30° to +80°C, R.H. < 95%
Housing
Dimensions 17.5 x 81 x 67.2 mm
Material PA66
Note: on the Y1 terminal is
mounted a flexible unipolar
red cable (N07V-K, 1 mm2,
40 mm in lenght, unsheated
sides)
Weight 75 g
Screw terminals
Tightening torque Max. 0.5 Nm according to
IEC EN 60947
CE Marking Yes
EMC Electromagnetic Compatibillity
Immunity According to EN 61000-6-2
Emissions According to EN 61000-6-3
General:
Power supply Overvoltage cat. II
Rated operational voltage (IEC 60664, IEC 60038)
through terminals A1, A2: 12 to 240 VDC + 10% -15%
and 12 to 240 VAC
+ 10% -15%, 45 to 65 Hz
Voltage interruption ≤ 10 ms
Rated operational power
AC supply: 4 VA
DC supply: 1.5 W
Supply:
Upper knob:
Setting of function:
Op- delay on operate
In - interval
Io - interval on trigger open
Id - double interval
Dr - delay on release
R - symmetrical recycler
(ON first)
Rb - symmetrical recycler
(OFF first)
Centre knob:
Time setting on relative scale:
1 to 10 with respect to the
chosen range.
Lower knob:
Setting of time range
Time Setting:
Specifications
Timing:
Time ranges
Knob selectable 0.1 to 1 s
1 to 10 s
6 to 60 s
60 to 600 s
0.1 to 1 h
1 to 10 h
10 to 100 h
Setting accuracy ≤ 5%
Repeatability ≤ 0.2%
Time variation
Within rated power supply ≤ 0.05%/V
Within ambient temperature ≤ 0.2%/°C
Reset
Manual reset of time and/or Close the trigger contact
relay between pins A1 and Y1
Pulse duration ≥ 100 ms
Power supply interruption ≥ 200 ms
Automatic start Connect pins A1 and Y1
Output 1xSPDT or relay
Rated insulation voltage 250 VAC (rms)
Contact Ratings (AgSnO2) µ
Resistive loads AC 1 5 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life ≥ 30 x 106 operations
Electrical life ≥ 105 operations
(at 5 A, 250 V, cos ϕ = 1)
Operating frequency < 7200 operations/h
Dielectric strength
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand
voltage 2.5 kV (1.2/50 µs)
Output:
QQ
:2
49
76
31
99
1
Specifications are subject to change without notice (11.01.07) 3
VIMT51
Operating Diagrams:
Powersupply
RelayON
Triggerinput
T T
LED
FunctionOp-Delayonoperate-Manualstart
Powersupply
RelayON
T T
LED
FunctionOp-Delayonoperate-Automaticstart
Powersupply
RelayON
Triggerinput
T T
LED
FunctionIn-Interval-Manualstart
Powersupply
RelayON
T
LED
FunctionIn-Interval-Automaticstart
T
ON
OFF
ON
OFF
ON
OFF
ON
OFF
FunctionIo-Intervalontriggeropen
Powersupply
RelayON
Triggerinput
T T
LED
FunctionId-Doubleinterval
Powersupply
RelayON
Triggerinput
T T
LED
ON
OFF
ON
OFF
FunctionDr-Delayonrelease
Powersupply
RelayON
Triggerinput
T
LED
Powersupply
RelayON
T T T T
LED
Triggerinput
FunctionRb-Symmetricalrecycler(OFFfirst)
Powersupply
RelayON
T T T T
LED
Triggerinput
ON
OFF
ON
OFF
ON
OFF
Function R - Symmetrical recycler (ON first)
QQ
:2
49
76
31
99
1
4 Specifications are subject to change without notice (11.01.08)
VIMT51
67.2
18.7
45
17.5
81
2
Dimensions:Wiring Diagram:
QQ
:2
49
76
31
99
1
本文档为【VITEKO宽电压多功能时间继电器VIMT51CW24】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。