and front panel mounting.
tage relays. 17.5mm wide housing suitable both for back
True RMS 3-Phase Multi-function
DPB51CM48
DPB51CM23
Property
Terminals L1, L2, L3
DPB 51 C M48DPB 51 C M23
• 17.5 mm DIN-rail housing
• Detects if all the 3-phase-phase voltages are within the
Supply ranges from 208 to 480VAC covered by two multivol-
phase loss,over and under voltage with built-in time delay.
3-phase line voltage monitoring relay for phase sequence,
1
Monitoring Relays
Product Description
• TRMS 3-phase over and under voltage,
phase sequence and phase loss monitoring relay
• Detects when all 3 phases are present and have the
correct phase sequence
• Upper and lower limits separately adjustable
• Measures its own power supply
• Selection of measuring range by DIP-switches
• Adjustable voltage on relative scale
• Adjustable delay function (0.1 to 30 s)
• Output: 5 A SPDT relay N.E.
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• LED indication for relay, alarm and power supply ON
Type Selection
Mounting Output Supply: 208 to 240 VAC Supply: 380 to 480 VAC
DIN-rail SPDT
Input
L1, L2, L3, N
Measures its own supply
Measuring ranges
177 to 275 VAC
VAC
Ranges
Upper level +2 to +22%
of the nominal voltage
Lower level -22 to -2%
of the nominal voltage
Note: The input voltage
must not exceed the maximum
rated voltage or drop below
the minumum rated voltage
reported above.
Hysteresis
Set points from 2 to 5% 1%
Set points from 5 to 22% 2%
Input Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2) μ
Resistive loads AC 1 5 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life ≥ 30 x 106 operations
Electrical life ≥ 105 operations
(at 5 A, 250 V, cos ϕ = 1)
Operating frequency ≤ 7200 operations/h
Dielectric strength
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 μs)
Output Specifications
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
45 to 65 Hz
45 to 65 Hz
Rated operational power
13 VA @ 230 VAC, 50 Hz
13 VA @ 400 VAC, 50 Hz
Supplied by L1 and L3
Supply Specifications
Type DPB51
set limits
L1, L2, L3
208 to 240 VAC ± 15%
M48 380 to 480 VAC ± 15%
M23
323 to 550
Administrator
Typewritten Text
http://www.dold-relay.com
DIP switches 1 as shown below.
Adjust the input range setting the DIP switches 3 and 4 as shown below. Select the desired power-on delay time setting the
absolute scale(0.1 to 30s).
Setting of delay on alarm time on Setting of upper level on relative scale.Setting of lower level on relative scale.
Reservation
exceeds the upper set level.
The relay releases in case of interruption of one or more phases,when one or more voltages drop below the lower set level or
(load monitoring)Example 2
The relay monitors over and under voltage,phase loss and phase sequence.
relay releases immediately. Only 200ms delay occurs. The failure is indicated by the red LED flashing 5Hz during alarm status.
at 2Hz and the output relay releases after the set delay time. If the phase sequence is wrong or one phase is lost.the output
If one or more phase-phase voltage exceeds the upper set level or drops below the lower set level,the red LED starts flashing
DPB51 operates when all 3 phases are present at the same time,the phase sequence is correct and the phase-phase voltage
levels are within the set limits.
Approx. 80 g
17.5 x 81 x 67.2 mm
DPB51
2
Upper knob: Centre knob: Lower knob:
Function/Range/Level and Time Delay Setting
Mode of Operation
Example 1 (mains network monitoring)
Environment
Degree of protection IP 20
Pollution degree 3
Operating temperature -20 to 60°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing
Dimensions
Material PA66 o Noryl
Weight
Screw terminals
Tightening torque Max. 0.5 Nm
according to IEC 60947
Product standard EN 60947-5-1
Approvals UL, CSA
CCC (GB14048.5)
CE Marking L.V. Directive 2006/95/EC
EMC Directive 2004/108/EC
EMC
Immunity According to EN 61000-6-2
Emissions According to EN 61000-6-3
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
Reaction time
Incorrect phase sequence or
total phase loss < 200 ms
Voltage level (input signal variation from
-20% to +20% or from
+20% to -20% of set value)
Alarm ON delay < 200 ms (delay < 0.1 s)
Alarm OFF delay < 200 ms (delay < 0.1 s)
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON LED, yellow
General Specifications
Power ON delay
ON: 6 s ± 0.5 s
OFF: 1 s ± 0.5 s
Measuring range
SW3 ON ON OFF OFF
SW4 ON OFF ON OFF
M48 380 VAC 400 VAC 415 VAC 480 VAC
M23 208 VAC 220 VAC 230 VAC 240 VAC
Administrator
Typewritten Text
http://www.dold-relay.com
111412
L3L2
Example 2 (load monitoring)
DPB51
3
Wiring Diagrams
Operation Diagrams
L2 L3L1
L1
L2
L3
L1
L3
m<3
�
11
12
U
L2 L3L1
L1
L2
L3
L1
L3
m<3
�
11
12
U
Example 1 (mains network monitoring)
5.
5
67.2
18.7
45
17.5
81
2
Dimensions
3
L1
14 14
Administrator
Typewritten Text
http://www.dold-relay.com
本文档为【DPB51_断相逆相过压欠压多功能相序保护器】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。