Error
code
Diag.
code Device Display Meaning for the LMV5x system Corrective action
01 01 LMV5… Internal Fault Basic Unit ROM error
Any # RAM error
01 RAM error in register bank 0 (LMV51...)
02 RAM error in IDATA area (LMV51...)
03 RAM error in XDATA area (LMV51...)
04 RAM error of variables used
05 RAM error variable consistency
06 RAM error reading back test pattern
07 Error RAM test code run
Any # Error in connection with data comparison (internal communication) between µC1 and µC2
01 TimeOut during program run synchronization prior to data transmission
02 TimeOut during data transmission
03 CRC error during data transmission
05 TimeOut during program run synchronization with initialization
10 Error counter "Flame intensity outside tolerance" has elapsed Check flame detector signal. If ok, and fault re-occurs, replace LMV5…
11 Error counter "Target phase unequal" has elapsed
12 Error counter "Reset-lockout input unequal" has elapsed
40 Fuel train unequal
41 Relay control word unequal
42 ROM-CRC signature unequal
43 Phase unequal
44 (Key + main loop counter) unequal
04 Unsuccessful synchronization of the 2 µCs
Fault with Base Unit (LMV5…)
02 LMV5... Internal Fault Basic Unit
LMV5... Internal Fault Basic Unit
If fault occurs continously, replace LMV5…
If fault occurs sporadically improve EMC. If fault occurs
continously, replace LMV5…
03
LMV Quick Start Guide Page 1 Section 5-2
Error
code
Diag.
code Device Display Meaning for the LMV5x system Corrective action
Any # Fault during test of the flame signal amplifier
01 Fault during test of the flame signal amplifier
02 Crosstalk fault between test pin and flame signal amplifier channel (with LMV52... FSVchannel QRI... / QRB...)
03 Crosstalk fault between test pin and FSV channel ION (Only LMV52...)
Any # Fault internal hardware tests
01 Fault during test of the ignition relay
02 Fault during test of the safety relay
03 Fault during voltage supervision test
04 Relay voltage not switched off after reset
Any #
Basic unit has detected an improper circuit at one of the
outputs, a faulty diode, or a short-circuit in the power supply of
the contact feedback network. The diagnostic codes indicates
the input affected
01 Load controller on / off
02 Fan contact
03 Selection of oil-firing
04 Selection of gas-firing
05 Reset
06 Pressure switch oil maximum
07 Pressure switch oil minimum
08 Pressure switch valve proving
09 Safety valve oil feedback
0A Fuel valve 1 oil feedback
0B Fuel valve 2 oil feedback
0C Fuel valve 3 oil feedback
0D Safety valve gas feedback
0E Fuel valve 1 gas feedback
0F Fuel valve 2 gas feedback
10 Fuel valve 3 gas feedback
11 Safety chain burner flange
12 Safety relay feedback
Internal Fault
Basic Unit
Fault with devices or wiring connected to the Base Unit (LMV5…)
Fault with Base Unit (LMV5…)
05 If fault occurs sporadically: Improve EMC. If fault occurs constantly: Replace flame detector or replace LMV5…
Fault Flame
Detector Test
LMV5… /
Flame
Dect.
Fault with Flame scanner (QRI) or Base Unit ( LMV5…)
If fault occurs sporadically improve EMC. If fault occurs
continously, replace LMV5…
10
Devices
conn. To
LMV5…
Internal Fault
Basic Unit
1) Check connections of the neutrals to all of the
connected switches, valves, etc...
2) Check for capacitive loads that cause voltage to be
present on the terminal after the LMV deenergizes the
terminal. If voltage exists on an output terminal, such as
a fuel valve, after the LMV denergizes the terminal, this
will cause a fault. Voltage must drop to zero on the
terminal within about 10 ms after the terminal is de-
energized.
06 LMV5…
LMV Quick Start Guide Page 2 Section 5-2
Error
code
Diag.
code Device Display Meaning for the LMV5x system Corrective action
13 Pressure switch gas minimum
14 Pressure switch gas maximum
15 Ignition transformer feedback
16 Fan pressure switch
17 Start release oil
18 Heavy oil direct start
19 Load controller open
1A Load controller closed
1B Start release gas
11 01 Basic unit has detected a short-circuit in the contact feedback network
Any #
Fault Positioning
Actuator or Fan
Speed not
reached
LMV5...has detected a positioning error on one or several
actuators. Could also be the VSD module if equipped
01-3F
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in
hexadecimal format) Indicated that more than one actuator /
VSD has problems.
01 Air Act. Positioning fault air actuator
02 Fuel Act. Positioning fault fuel actuator
04 Aux1 Act. Positioning fault auxiliary actuator 1
08 Aux2 Act. Positioning fault auxiliary actuator 2
10 VSD module
Fan Speed Not
Reached
The fan in combination with the VSD has not reached the
required speed
20 Aux3 Act. Fault Positioning Actuator Positioning fault auxiliary actuator 3
If error occurs on one actuator only :
1) Ensure torque requirements of dampers / valves is
less than Actuator output.
2) Verify that no damper / valve is bound.
3) Replace actuator.
If error occurs on multiple actuators (01-3F) :
1) Verify that the CanBus wiring is correct.
2) Verify that shields (screens) on CanBus cable are
connected properly.
If error occurs on VSD :
1) Check speed sensor on motor for correct installation,
especially gap between sensor and wheel.
2) Check for filters, damping and or delays on the input
signal to the VSD. The VSD should respond to the input
signal in a linear fashion.
15 Fault Positioning
Actuator
Fault with devices or wiring connected to the Base Unit (LMV5…)
Fault with Connected actuators or VSD
Devices
conn. To
LMV5…
Internal Fault
Basic Unit
Act. /
VSD
Control
10
1) Check connections of the neutrals to all of the
connected switches, valves, etc...
2) Check for capacitive loads that cause voltage to be
present on the terminal after the LMV deenergizes the
terminal. If voltage exists on an output terminal, such as
a fuel valve, after the LMV denergizes the terminal, this
will cause a fault. Voltage must drop to zero on the
terminal within about 10 ms after the terminal is de-
energized.
LMV Quick Start Guide Page 3 Section 5-2
Error
code
Diag.
code Device Display Meaning for the LMV5x system Corrective action
Any # Basic unit has detected a plausibility fault in the ratio control system.The diagnostic code describes the cause of the fault.
00 Ratio curve of the air actuator is not fully defined
01 Ratio curve of the fuel actuator is not fully defined
02 Ratio curve of auxiliary actuator 1 is not fully defined
03 Ratio curve of auxiliary actuator 2 is not fully defined
04 Ratio curve of auxiliary actuator 3 is not fullydefined
05 VSD curve is not fully defined
0A Calculated P-part outside the permissible range
0B Calculated I-part outside the permissible range
0C Calculated system delay time outside the permissible range
0D Calculated O2 setpoint outside the permissible range
0E Calculated O2 min. value outside the permissible range
0F Calculated O2 ratio value outside the permissible range
03 The load / point number predefined by the AZL… lies outside the permissible range
If fault occurs sporadically improve EMC. If fault occurs
continously, replace LMV5…
14 Calculated standardized value lies outside the permissible range
Check if the correct values have been entered for the
standardized values.
Readjust O2 trim control, if required, or repeat the
settings
20 With hysteresis compensation: Permissible target positioning range exceeded
21 The load / point number predefined by the AZL… lies outside the permissible range
22 With a switch instruction, none of the defined cases was satisfied
23 With the switch instruction, no defined ratio control phase has been identified
40 Unplausible target positions
16 LMV5…
Insure that actuators that are addressed and activated
have their positions defined. Check curve points to see if
correct values have been entered for the actuator or
VSD. Readjust the ratio curve, if required
If fault occurs sporadically improve EMC. If fault occurs
continously, replace LMV5…
Internal Fault
Basic Unit
Check parameters ( P Low-Fire, I Low-Fire, Tau Low
Fire, P High-Fire, I High-Fire, Tau High-Fire) These
values nomally self-set when the delta-time is
measured. Check the values of these parameters
against the maximum and minimum ranges. Readjust
O2 control curve if necessary.
The O2 control curve must be 1% O2 lower than the %
O2 measured at the ratio control curve, and 0.5% above
the O2 guard curve. Readjust curves.
Fault with Base Unit (LMV5…) Ratio Control, O2 Trim, VSD
LMV Quick Start Guide Page 4 Section 5-2
Error
code
Diag.
code Device Display Meaning for the LMV5x system Corrective action
Any # (Internal) communication error of ELV
3F Detection of different data when making the data comparison
01 Timeout with program synchronization prior to data transmission
02 Timeout with data transmission
03 CRC fault during data transmission
18 Any # Invalid Curve Data Corruption in the combustion curve data
Vaules on curve should be within 0.0 % - 100.0 % for
load and VSD, 0.0° - 90.0° for actuators. If possible,
adjust curve values back into the valid range. If this fault
occurs on a unit that was functioning correctly after
commisioning, replace LMV5...
Any #
Basic unit (ratio control system) has detected a fault
when comparing potentiometer channels A and B. Diagnostic
code shows on which actuator the fault occurred. See
diagnostic code
01..2F
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in
hexadecimal format)
01 Air Act.
02 Active Fuel Act.
04 Aux 1 Act.
08 Aux 2 Act.
20 Aux 3 Act.
Fault with Actuator or CANBus cabling
Act.
Internal Fault
Actuator
Fault with Base Unit (LMV5…)
If fault occurs sporadically improve EMC. If fault occurs
continously, replace LMV5…17
Internal Fault
Basic Unit
LMV5…
19
1) Check CANBus cabling. Ensure that all cable shields
(screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and at
the LMV5x...
2) Check each CANBus Connector to ensure proper
termination (no conductors exposed on the back of the
plug)
3) If fault occurs sporadically: Improve EMC.
4) If fault occurs constantly: Replace actuator according
to diagnostic code.
Fault occurred on the indivudual actuator (see diagnostic code)
when comparing potentiometer channels A and B
LMV Quick Start Guide Page 5 Section 5-2
Error
code
Diag.
code Device Display Meaning for the LMV5x system Corrective action
1A 01 Slope too steep A section of actuator curve is too steep.
Check maximum slope sections of actuator curves.
Maximum allowabe slopes are as follows:
- 3.6° per 0.1 % Load (30 sec ramp)
- 1.8° per 0.1 % Load (60 sec ramp)
- 0.9° per 0.1 % Load (120 sec ramp)
If these maximums are exceeded, adjust curve section
below these maximum slopes.
1B Any #
Operation in
Parameter
Setting Mode Quit
Curve Parameters (actuator curves) programming mode is still
active in Phase 62 (drive to low fire and shutdown) and the
target positions (normal operation) have not been reached.
When setting the curve parameters, the plant should be
operated in manual mode with “Burner on“. This
prevents the internal load controller from triggering the
change to shutdown. Response of the internal
Temperature Limiter can trigger this same fault.
However, the curve point currently being set can still be
stored in standby or lockout.
Any # Ignition positions for activated actuators (or VSD) have not been set. See diagnostic code to indicate the faulted actuator.
01..3F
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in
hexadecimal format)
01 Ignition position for air actuator not set.
02 Ignition position for active fuel actuator not set.
04 Ignition position for aux1 actuator not set.
08 Ignition position for aux2 actuator not set.
10 Ignition position for VSD not set.
20 Ignition position for aux3 actuator not set.
Fault with Actuator (VSD) Positioning, Actuator (VSD) Run Time
Ignition Pos not
defined
Set the ignition position of the actuator(s). The ignition
positions for each fuel are independent, and the
positions are also independent of the low fire position.
LMV5…
1C
LMV Quick Start Guide Page 6 Section 5-2
Error
code
Diag.
code Device Display Meaning for the LMV5x system Corrective action
Any # Running time fault of actuators or VSD.
01..3F
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in
hexadecimal format)
01 Fault Running Time Air Actuator Running time fault of air actuator
04
Fault Running
Time Aux
Actuator
Running time fault of auxiliary actuator 1
08
Fault Running
Time Aux
Actuator
Running time fault of auxiliary actuator 2
10 VSD / LMV5..
Fault Running
Time VSD Running time fault of VSD
20 Act. / LMV5...
Fault Running
Time Aux
Actuator
Running time fault of auxiliary actuator 3
Any #
Act. /
LMV5.. /
VSD
Basic unit has detected that 1 / several actuators (incl. VSD
module) has / have not reached the special position pertaining
to the Phase
01..3F
The diagnostic value is made up of the following faults or their
combinations (the individual diagnostic codes are added up in
hexadecimal format)
01 Positioning fault of air actuator
02 Positioning fault of fuel actuator
04 Positioning fault of auxiliary actuator 1
08 Positioning fault of auxiliary actuator 2
10 VSD Sys. VSD has not reached the speed
20 Act. Positioning fault of auxiliary actuator 3
1) Check parameters (TimeNoFlame) and
(OperatRampMod). These should be set to values
greater than the ramping timeof the attached actuators
or VSD.
2) Check connected actuators to determine if their
torque rating is being exceed (stuck damper or valve
etc...)
3) Check the two 12V fuses located under black covers
on the right side of the LMV5...
4) Check the CANBus power supply (blue or black
transformer) Pin 1 and Pin 4 should have 12VAC to
reference ground which is pin 2. Voltage betwen Pin 1
and Pin 4 should be 24VAC.
Fault with Actuator (VSD) Positioning, Actuator (VSD) Run Time
LMV5…/
Act./ VSD
Fault Running
Time
Act. /
LMV5...
1D
1) Check connected actuators to determine if their
torque rating is being exceed (stuck damper or valve
etc...)
2) Check the two 12V fuses located under black covers
on the right side of the LMV5...
3) Check the CANBus power supply (blue or black
transformer) Pin 1 and Pin 4 should have 12VAC to
reference ground which is pin 2. Voltage betwen Pin 1
and Pin 4 should be 24VAC.
4) If a VSD is being used, check for filters, damping and
or delays on the input signal to the VSD. The VSD
should respond to the input signal in a linear fashion.
See Error Code 15
Act. Special Pos not
reached1E
LMV Quick Start Guide Page 7 Section 5-2
Error
code
Diag.
code Device Display Meaning for the LMV5x system Corrective action
Any # VSD Sys. Code for VSD Module Fault
Basic unit has detected a fault in connection with the VSD
module
01 VSD Module
Speed Acquisition
faulty Internal VSD module test was not successful
02 Wrong Direction of Rotation Fan rotates in the wrong direction
1) Check to see if the motor’s direction of rotation is
correct. Reverse if necessary
2) Check to see if the arrow on the speed wheel points
in the correct direction of rotation. Reverse if necessary.
03 Speed Acquisition faulty
Pulse sequence and length at the speed input were different
from those anticipated
04
Standardization
canceled because
of VSD
Fan was not able to keep the standardized speed at a constant
level
05
Standardization
canceled because
of Air Actuator
Air actuator (or air influenced actuator) has not reached the
prepurge position.
For this reason, speed standardization is not possible
1) Check to see if all air-influencing actuators travel to
the prepurge position and remain in that position for the
VSD standardization.
2) Ensure torque requirements of air influencing
dampers / valves is less than Actuator output.
3) Verify that no air influencing damper / valve is bound.
4) Check CanBus power suppy and CanBus fuses (FU 2
and FU3)
06
Speed Test was
not successfully
completed
Internal VSD module speed test was not successful If fault occurs sporadically improve EMC. If fault occurs continously, replace LMV5…
21 Any # Safety Loop open Limit switches wired into the saftey loop have opened (such as low water or High Limit)
Check all switches wired into the saftey loop circuit. This
also includes the burner flange circuit.
22 Any #
Internal Temp
Limiter
has responded
Internal TL has switched off because parameterized value has
been exceeded
Check the burner / boiler temperature, sensor located
on Input 1 and / or Input 4
Devices
conn. To
LMV5…
If fault occurs sporadically improve EMC. If fault occurs
continously, replace LMV5…
1) Check the gap between the speed wheel and the
sensor. The gap shold be about 1/16" of an inch (2mm)
or about two turns out.
2) Check the wiring of the speed sensor. Ensure
reference ground is connected.
Fault with devices or wiring connected to the Base Unit (LMV5…)
1F
VSD Sys.
Fault with VSD Module
LMV Quick Start Guide Page 8 Section 5-2
Error
code
Diag.
code Device Display Meaning for the LMV5x system Corrective action
Any # Extraneous Light on Startup Basic unit has detected extraneous light during startup
00 Extraneous Light on Startup Basic unit has detected extraneous light during startup
01…
03
Extraneous Light
on Startup
(LMV52 only) Basic unit has detected extraneous light during
startup 0 = QRI, 1 = ION or UV, 2 = Both
Any # Extraneous Light on Shutdown Basic unit has detected extraneous light during shutdown
00 Extraneous Light on Shutdown Basic unit has detected extraneous light during shutdown
01…
03
Extraneous Light
on Shutdown
(LMV52 only) Basic unit has detected extraneous light during
shutdown 0 = QRI, 1 = ION or UV, 2 = Both
Any # No Flame at End of Safety Time No flame detected at the end of safety time TSA1
00 No Flame at End of Safety Time No flame detected at the end of safety time TSA1
01…
03
No Flame at End
of Safety Time
(LMV52 only) No flame detected at the end of the safety time. 0
= QRI, 1 = ION or UV, 2 = Both
Any # Loss of flame during normal operation (Phase 60-62)
00 Loss of flame during normal operation (Phase 60-62)
01…
03
(LMV52 only) Loss of flame during operation detected. 0 = QRI,
1 = ION or UV, 2 = Both
27 Air Pressure on Air pressure = on, but should have been off
28 Air Pressure off Air pressure = off, but should have been on
29 Fan Contactor Contact is on FCC signal = on, but should have been off
2A Fan Contactor Contact is off FCC signal = off, but should have been on
Any #
Fault with devices or wiring connected to the Base Unit (LMV5…)
1) Ensure that the source of extraneous light is not a
flame. If it is a flame, take corrective action immediately.
2) If the QRI scanner is used, ambient light can cause
an extraneous light error. Ensure sensor is viewing a
dark area such as the inside of a boiler.
3) If the QRI scanner is used, check for glowing
refractory. If glowing refractor is the cause, the postburn
time may need to be lengthened or a UV scanner may
have to be used.
1) With a piloted gas train, this means that the pliot did
not light. Check wiring of ignition transformer and pilot
valve.
2) Check manual shutoff valves for the pilot gas.
3) Check position of air damper. Close further if
necessary. Pilot may be blowing out.
4) Check flame detector for signal in the presence of
flame using a flame source. Replace if detector does no
本文档为【QSG Section 5-2 Error】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
该文档来自用户分享,如有侵权行为请发邮件ishare@vip.sina.com联系网站客服,我们会及时删除。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。